Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T17CM02322
Parcel: 12616303A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM02322
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved. Detail 2/P5.0 calls for the installation of Watts 8A vacuum breakers at the clothes washer connection but this is not an appropriate application due to the continuous backpressure. Reference: Section 303.2, IPC 2012. [Second comment: Comment not resolved. The generic detail shows how to determine the size of the water hammer arrestors and how to install them but nothing calls for their installation at the clothes washer connection. (Note: detail 2/P5.0 calls for the installation of Watts 8A vacuum breakers at the clothes washer connection but this is not an appropriate application due to the continuous backpressure.)] [Initial comment: Provide pressure-absorbing devices for the water connections to appliances equipped with quick acting or solenoid valves (e.g. clothes washers). Reference: Section 604.9, IPC 2012.]
2. The detail does not show how the sump pump installation will comply with the requirements of Section 712, IPC 2012. The detail shall show the check valve and shut off valve, the discharge pipe and its connection to the building sewer, the sump vent, and the connection of the building subdrains to the sump. The plumbing plan does not clearly show the where the sump is to be located and how the subdrains are to be routed from the plumbing fixtures to the sump. In fact, the labels in the plumbing plan appear to show two SP-1 units located in the basement. [Second comment: Provide a detail showing that the installation of the proposed duplex sewage pump, SP-1 complies with the requirements of Section 712, IPC 2012.] [Initial comment: The architectural plans indicate the installation of a restroom and other plumbing fixtures in the basement of building #2. Provide a plumbing design for the basement.]Comment not addressed. [Initial comment: There are six apartments in building #9; are there only two that have gas ranges? Reference; Section 107.2.1, IBC 2012.]
07/14/2017 ROBERT SHERRY WATER REVIEW Completed
07/14/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/18/2017 SSHIELD1 ZONING HC REVIEW Passed
07/18/2017 STEVE SHIELDS ZONING REVIEW Approved
07/27/2017 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/27/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 2; Sheets a3.0 through a3.4; Wall Legend: Several wall types still indicate wood studs at 18" o.c. Sheets a3.0, a3.1, a3.2, and a3.3 revised those spacings to 16" o.c., but Sheet a3.4 was not revised. Please verify.