Permit Number: T17CM02320
Parcel: 12616303A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM02320
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Replot the unit plumbing plans so that the floor plan of the apartment is visible for reference and orientation. Reference: Section 107.2.1, IBC 2012.
2. Provide the IPC fixture unit calculations for building #7. Reference: Section 107.2.1, IBC 2012.
3. Provide third-party listing and material standards for all plumbing fixtures being installed. Reference: Sections 303.4 and 402, IPC 2012.
4. Revise the design criteria of the water distribution system to provide a flow pressure of 15 PSI or the flow pressure prescribed by the fixture or appliance manufacturer, whichever is greater. Reference: Section 604.3, IPC 2012, as amended by the City of Tucson.
5. The water system design appears to be based on the use of Type L copper tubing but the recirculation note on sheet P1.1 refers to the use of PEX tubing. If PEX tubing is to be used, provide a table showing the correct PEX tubing sizes to be used. Reference: Sections 303.2 and 604.3, IPC 2012.
6. Provide pressure-absorbing devices for the water connections to appliances equipped with quick acting or solenoid valves (e.g. clothes washers). Reference: Section 604.9, IPC 2012.
7. Provide a full-open valve for the water supply entrance to each dwelling unit unless each fixture is equipped with stop valves. Show the location of the full-open valve. Reference: Section 606.1(6), IPC 2012.
04/20/2017 ROBERT SHERRY WATER REVIEW Reqs Change Clarify the water supply configuration of the apartments. Is each apartment (or building) individually metered with a single backflow prevention assembly located at the Tucson Water meter?
04/20/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Replot the unit mechanical plans so that the floor plan of the apartment is visible for reference and orientation. Reference: Section 107.2.1, IBC 2012.
2. The mechanical floor plan for the apartment has a keynote symbol "3"; what does this signify? Reference: Section 107.2.1, IBC 2012.
3. Revise the ventilation calculations for the Type F apartments in building #7. Revise the intermittent ventilation rate factor per Table M1507.3.3 (2), IRC 2012.
4. Provide exhaust for the residential kitchens per Table 403.3, IMC 2012 (i.e. 100 CFM intermittent or 25 CFM continuous). Reference: Section 403.3, IMC 2012.
5. The dryer vent does not appear to be terminating at the roof of the apartment, revise detail 1/M4.0 to show how the vent terminates. Reference: Section 107.2.1, IBC 2012.
6. Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.6.5, IMC 2012