Permit Number: T17CM02186
Parcel: 12411021E

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T17CM02186
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating/cooling load calculations to justify the capacities of the new rooftop units. Reference: Section C403.2, IECC 2012.
2. Provide calculations to show that the suite has adequate ventilation. Reference: Section 403.3, IMC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/24/2017 MMENDIB1 OUT TO CUSTOMER Completed