Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM02186
Parcel: 12411021E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM02186
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2017 KEN BROUILLETTE FIRE REVIEW Approved
03/30/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
04/03/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle (e.g. a 30-second cycle at 0.5 GPM will deliver 0.25 gallons). Verify that the specified automatic faucet will operate for a minimum time of 10-seconds; with a flow rate of 0.5 GPM and a maximum delivery of 0.083 gallons, the cycle will not last for the required 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. The specified water heater, WH-2, may not comply with the requirements of Section 607.1, IPC 2012 because it will not be activated until the flow rate exceeds 0.65 GPM.
04/04/2017 ROBERT SHERRY WATER REVIEW Completed
04/04/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Condensate drains shall be terminated at an approved disposal location. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter itself terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
2. Provide calculations to show that adequate ventilation will be provided for the occupied spaces. Reference: Sections 401.2 and 403.2, IMC 2012 and Section C403.2.5, IECC 2012.
3. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012.
4. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
5. Clarify how excess outside air relief from the building is to be accomplished from each rooftop unit without the relief air being recirculated into the rooftop unit. Reference: Section C403.3.1.1.4, IECC 2012.
04/05/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G0.1; CODE DATA: PLEASE ADD THE 2009 ICC/ANSI A117.1 ACCESSIBILITY CODE TO THE CODES LISTED.
2. SHEET G0.1; DEFERRED SUBMITTALS: SINCE IT APPEARS THE NEW ROOF TOP UNITS ARE SIZED AND LOCATED (SEE MECHANICAL SHEETS), THE STRUCTURAL CALCULATIONS INVESTIGATING THE ADEQUACY OF THE EXISTING ROOF STRUCTURE SHOULD BE PROVIDED WIWTH THIS SUBMITTAL.
3. SHEET A2.0; FLOOR PLAN: PER THE IBC TABLE 2902.1, A DRINKING FOUNTAIN IS REQUIRED FOR THIS TENANT SPACE (HI/LO OR SINGLE POINT OF USE DISPENSER CONNECTED TO A WATER LINE). NONE WAS LOCATED ON THE FLOOR PLAN. PLEASE VERIFY.
4. SHEET A2.0; DETAIL 2: PLEASE INDICATE HOW THE SLIP CONNECTION IS ATTACHED TO THE ROOF STRUCTURE.
5. SHEET A2.0; FLOOR PLAN NOTES: NOTE 3 INDICATES TO SEE A2.0-2 FOR THE PARTITION WALL. THAT DETAIL INDICATES TO SEE THE STUD FRAMING SCHEDULE FOR THE STUD DESIGN. PLEASE INDICATE ON THE DRAWING WHERE THIS FRAMING SCHEDULE IS LOCATED.
6. SHEET A2.1; RESTROOM FIXTURE ELEVATIONS: PLEASE ENLARGE THE DIMENSION FOR THE LOCATION OF THE TOILET PAPER DISPENSER (3/32" MINIMUM).
7. SHEET A3.0; DIGITAL DISPLAY DETAILS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32' IN HEIGHT. PLEASE REVISE.
8. SHEET A5.0; DETAILS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32' IN HEIGHT. PLEASE REVISE.
9. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/11/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved