Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM02151
Parcel: 10612199B

Address:
1557 W PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM02151
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2017 KEN BROUILLETTE FIRE REVIEW Reqs Change The occupant loads on the cover sheet and sheet A0.0 do not match. Please clarify.
Please add note to cover sheet indicating the fire sprinkler and fire alarm revisions are a deferred submittal to the State Fire Marshal.
04/11/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change T17CM02151
ACADEMY OF MATH/SCIENCE TI
1. Sheet T1.0; Code Review Checklist: Please revise the allowable area as indicated at 42,750 SF. The allowable area = 9500 + 3(9500) + 0.75(9500) = 45,125 SF. Please verify.
2. Sheet T1.0; Building Occupancy: With an occupant load of 783, the IBC Section 1021.2.4 requires only three exits (occupant load between 501 and 1000). Please verify.
3. Sheet C1.0; Zoning Summary: The maximum height is listed as 70'-0". Is this an allowable maximum height required by zoning? It appears to be an actual building height. Please verify the allowable building height using the IBC Table 503.
4. Sheets D1.0 and D1.1; Demolition Plan Keynotes: Note 4 was not located on the plans. Please verify.
5. Sheets A0.0 and A0.1; Plan Note: A note indicates 'this plan applies for a building official reduction in the total computed occupant load to 783…..'. Has an appeal been submitted to the building official concerning this issue? A decision from the building official must be provided before this permit can be approved.
6. Sheets A0.0 and A0.1; Occupant Load: If the appeal to allow an occupant load of 783 is denied, exiting and plumbing fixture calculations will require revisions on the drawings.
7. Sheets A0.0 and A0.1; Required Number of Exits: Per the IBC Section 1021.2.4, three exits are required. Please revise those sheets.
8. Sheet A0.1; Add Alt. Number 1 Life Safety Plan: Please indicate on the life safety plan where the add alt. number 1 will be located.
9. Sheets A2.0 and A2.1; Floor Plan: Wall type W4 was not located on either plan. Please verify.
10. Sheet A2.2; Reflected Ceiling Plan Add Alt. #1: Please indicate the exit sign at the north exit door, and add the symbol to the symbol legend.
11. Sheets A2.3 and A2.4; Ceiling Plan Symbol Legend: Please add the exit sign symbol to the legend.
12. Sheets A4.0 and A4.1; Restroom Plans and Elevations; Sheet A6.0 (Accessibility Details): Please verify the existing and the new grab bars are correctly located for adults and children where required. Verify water closets, lavatories, and drinking fountains meet the requirements for adults and children of the 2009 ICC/ANSI A117.1, Chapter 6.
13. Sheet S1.0; Structural Notes (Foundations): Note 1 indicates a soil report was provided for this project. Please provide one copy of the report for review.
14. Sheet S2.0 (Foundation Plan); Sheet A2.0 (Floor Plan): The architectural plan indicates the infill of an existing opening in the southwest corner of the building (note 33). The structural plan does not indicate that infill. Please coordinate.
15. Sheet S3.0: Please enlarge this sheet.
16. Sheet S4.0: Please revise the drawing title to foundation and framing details.
17. Sheet S4.0; Detail 206: Are the new 2x8 members to be connected to the existing joists? If so, please indicate the size, quantity, and spacing of the connectors. If not, please indicate on the detail.
18. General: Please provide written responses to all review comments.
04/13/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref: Plan sheet ED2.1, Demolition Keynote #3. Calls for existing panel (1533) to remain, and to provide new 3-phase panel and feeders. Please clarify.
#2. Ref: Plan sheet ED2.2, Demolition Keynote #2. Calls for replacing panel E, Base bid and Alt. Panel E is not shown on the Alt one line diagram.
#3. Ref: Plan sheet E1.1, Power Keynotes #2, #3, #5. References to plan sheet ED3.1. No plan sheet ED3.1 located in the plan documents.
#4. Ref: Plan Sheet E1.2, Power Keynote #2. References to plan sheet ED3.2. No plan sheet ED3.2 located in the plan documents.
#5. Ref: Plan Sheet E3.1, Power Keynote #2. References to One Line Drawing plan sheet E5.1. E5.1 is the HVAC plan. Keynote #3, call for existing panel 1533 to remain, provide new feeders and 3 phase panel. Please clarify.
#6. Ref: Plan Sheet E6.2. One of the 400 amp panels is not identified on the one line diagram.
#7. Ref : Plan Sheet E6.3. The panel schedule for panel AC shows #10 AWG conductors on a 50 amp circuit breaker, circuits 14, 16, 18. The conductors are undersized per NEC 310.15B16.
#8. Ref: Plan Sheet E1.2 and E2.1. Verify that the rated color temperature output of all the exterior light sources comply with section 402.1 (3500K). TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE.
Ref: 2012 IBC 107.2.1, 2011 NEC, TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE
Dan.santacruz@tucsonaz.gov
04/14/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
04/14/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/14/2017 ROBERT SHERRY WATER REVIEW Approved
04/14/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/14/2017 GERRY KOZIOL WWM REVIEW Reqs Change The following is needed for Sewer Connection Fee Application Approval:



Need to show location, size and serial number of all water meters on the property.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/24/2017 MMENDIB1 OUT TO CUSTOMER Completed