Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T17CM02069
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/08/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide sealed drawings. 2. Provide the gas input and developed pipe length for each unit heater. 3. Revise the horizontal gas dirt leg detail per Section 408.4, IFGC 2012. 4. Show that the building envelope complies with Section C402, IECC 2012. 5. Provide a mechanical design, including heating load calculations, for the installation of the new unit heaters. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/07/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |