Permit Number: T17CM02069
Parcel: 12915006G

Review Status: Active

Review Details: COMMERCIAL - NEW

Permit Number - T17CM02069
Review Name: COMMERCIAL - NEW
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2017 KEN BROUILLETTE FIRE REVIEW Reqs Change Please provide a site plan indicating locations of existing and/or proposed fire hydrants.
Please update design criteria information to include current codes adopted by the city of Tucson (cover sheet)
PLEASE spell Tucson correctly (cover sheet)
03/30/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: UPS Expansion
T17CM02069
Building Plan (1st Review)

TRANSMITTAL DATE: March 30, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. It appears that the building plan matches the proposed development package DP17-0035 but until the development package has been approved Zoning cannot approve the building plan.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
03/30/2017 LOREN MAKUS ENGINEERING REVIEW Reqs Change DP must be approved first.
04/06/2017 FRODRIG2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/12/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Passed
04/12/2017 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Completed
04/12/2017 CTREVIL1 WATER REVIEW Passed
04/12/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide a site plan showing building location with respect to property lines to determine fire-resistance rating requirement for exterior wall based on fire separation distance (Table 602), or utility connections.
2. The structural calculation for the footing claims a soil bearing capacity of 2500 PSF. Provide a soils report to support this design criteria.
3. Sheet C1.0: Referenced codes do not reflect the currently adopted standards for the City Of Tucson. Please revise.
4. Sheet A1.0: Provide critical building heights, including finished floor elevation, top of wall and ridge height.
5. Sheet A2.0, A2.1: The footing shown are generic and don't show depth below grade. Please identify the depth of all footings.
04/12/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/18/2017 CTREVIL1 APPROVAL SHELF Completed
04/18/2017 CTREVIL1 OUT TO CUSTOMER Completed