Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM02023
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/14/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 03/14/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the sequence of operation for the relocated restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012. 2. Clarify the outside air flow rate for each heat pump. The ventilation calculations call for a total of 470 CFM of outside air but keynote 1 indicates that each heat pump is to be balanced with 275 CFM of outside air. 3. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2012. |
| 03/14/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/14/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 03/14/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A-1; KEYNOTE 49: A HIGH/LOW DRINKING FOUNTAIN OR A SINGLE POINT OF USE WATER DISPENSER (CONNECTED DIRECTLY TO A WATER LINE BUT NOT REQUIRING A DRAIN) IS REQUIRED. PLEASE INDICATE THIS ON THE NOTE, AND INDICATE CUPS AT AN ACCESSIBLE HEIGHT. 2. SHEET A-1; KEYNOTE 30: THIS NOTE WAS NOT LOCATED ON THE PLAN. PLEASE VERIFY. 3. SHEET A2.1; DETAIL 17: PLEASE ADD A DETAIL INDICATING THE WATER HEATER PLATFORM AND HOW IT CONNECTS TO THE WALL. 4. SHEET A-2.1; ELEVATIONS 1, 8, 9, 10, 13, 14, 16, 20; SECTION 4: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 5. SHEET H-1; SECTIONS 8 AND 17: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/14/2017 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Verify the size of the existing water meter serving this building. 2. Verify the minimum water pressure for this site; per Tucson water it is closer to 49 PSI. 3. Provide the total demand that will be served by this meter. |
| 03/14/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Clarify the backflow system detail on sheet P2; if no chairs are being supplied with water from this system, remove "chairs" from the notes. |
| 03/14/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/14/2017 | GERRY KOZIOL | WWM | REVIEW | Completed | |
| 04/11/2017 | MARTIN BROWN | FIRE | REVIEW | Approved |