Permit Number: T17CM01963
Parcel: 11308160C

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T17CM01963
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide lighting controls for the restroom exhause fan as required per mechanical comments.
04/16/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/16/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the control of the exhaust fan so that the fan runs whenever air is supplied to the restroom. Reference: Section 403.2.1 (4), IMC 2012.