Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2018 KELLY LEE ZONING REVIEW Approved
04/09/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. All plumbing fixtures shall be 3rd party listed.
2. Provide a drain for the water heater pan.
3. The length of the water cycle for the lavatory shall be at least 10-seconds for accessibility.
04/09/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments.#1. Provide timer control for the restroom fan as per mechanical comments.
#2. Provide color temperature requirement for exterior lighting as required per section 402.1 of the Outdoor Lighting Code.
04/09/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/09/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the control of the exhaust fan so that the fan runs whenever air is supplied to the restroom.
2. Provide a detail showing how the supports for AH-1 are connected to the roof structure.