Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T17CM01963
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2018 | KELLY LEE | ZONING | REVIEW | Approved | |
| 04/09/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. All plumbing fixtures shall be 3rd party listed. 2. Provide a drain for the water heater pan. 3. The length of the water cycle for the lavatory shall be at least 10-seconds for accessibility. |
| 04/09/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments.#1. Provide timer control for the restroom fan as per mechanical comments. #2. Provide color temperature requirement for exterior lighting as required per section 402.1 of the Outdoor Lighting Code. |
| 04/09/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/09/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the control of the exhaust fan so that the fan runs whenever air is supplied to the restroom. 2. Provide a detail showing how the supports for AH-1 are connected to the roof structure. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/16/2018 | BLARSON1 | OUT TO CUSTOMER | Completed |