03/15/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Indicate what is new and existing electrical equipment on the electrical plan.
#2. Provide complete compliance with the 2012 IECC for lighting.
#3. Provide compliance with the Tucson/Pima County Outdoor Lighting Code. See section 104 for plan submittal requirements. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd.
#4. Locate the electrical service, panel, all mechanical equipment on the electrical floor plan. Designate circuit numbers, wiring type, conductors, conduit, disconnects, sizes and types.
#5. Locate the smoke detectors if applicable.
#6. Provide electrical load calcs.
Ref: 2012 IBC sec 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code, 2012 IECC.