Permit Number: T17CM01963
Parcel: 11308160C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM01963
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2017 MARTIN BROWN FIRE REVIEW Approved
04/17/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/17/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A2.0 (South Elevation Proposed); Sheet A1.0 (Foundation Construction Plan): The south elevation does not indicate a window in the southeast corner as indicated on the construction plan. Please clarify.
2. Sheet A2.0; Wall Section 5: Please indicate on a plan or elevation the location of the wall section cut.
3. Sheet S2.0; Wood Truss Schedule: Please include in the truss schedule the truss girders mark, configuration, spacing, and remarks.
4. Sheet S3.0; Detail 103: Please indicate the slab thickness over the concrete pedestal.
5. Sheet S3.0; Detail 106: Please indicate the new slab thickness at the wall.
6. Sheet S3.0; Details 105, 106, and 107: Should the new concrete slab be thickened at the wall (per Detail 106) on each of these details? Please verify.
7. Sheet S3.0; Detail 108: Note 2 references Detail 108. Please revise that reference number.
8. Sheet S3.0; Detail 205: Please add to note 4 to reference architectural for the structural height.
9. Sheet S3.0; Detail 206: Please add note 4 to the detail.
10. Sheet S3.0; Detail 207: Please indicate in note 5 the epoxy anchor embedment length into the masonry wall (or reference Detail 202).
11. General: Please provide written responses to all review comments.