Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM01947
Parcel: 14044009L

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM01947
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2017 MARTIN BROWN FIRE REVIEW Approved
03/28/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET X1; CODE REVIEW CHECKLIST (OCCUPANCY): THIS SHEET INDICATES AN OCCUPANCY CLASSIFICATION OF A2, THEN INDICATES AN M OCCUPANCY UNDER NUMBER 3. PLEASE COORDINATE.
2. SHEET X1; CODE REVIEW CHECKLIST (TYPE OF CONSTRUCTION): A NOTE INDICATES AN AREA INCREASE OF 300% DUE TO THE AUTOMATIC SPRINKLERS. IT IS ACTUALLY AN INCREASE OF 300% (IBC SECTION 506.3) IN ADDITION TO THE BASE ALLOWABLE SQUARE FOOTAGE (THE ACTUAL ALLOWABLE SF IS 27,000 + 9000 = 36,000 SF). PLEASE REVISE THE NOTE.
3. SHEET X1; CODE REVIEW CHECKLIST (EXITS/OCCUPANT LOADS): PLEASE USE 47 FOR THE OCCUPANT LOAD.
4. SHEET A1; EXITING PLAN: A NOTE BELOW THE PLAN INDICATES AN EXIT DISTANCE AND A COMMON EXIT TRAVEL DISTANCE. PLEASE REVISE THE NOTES. TABLE 1014.3 INDICATES THE COMMON PATH OF EGRESS TRAVEL TO BE 75 FEET MAXIMUM, AND TABLE 1016.2 INDICATES THE EXIT ACCESS TRAVEL DISTANCE TO BE 250 FEET MAXIMUM. PLEASE REVISE THE NOTES.
5. SHEET A1; FLOOR PLAN KEY NOTES: NOTE 5 WAS NOT LOCATED ON THE PLAN. PLEASE VERIFY.
6. SHEET A1; FLOOR PLAN KEY NOTES: NOTE 7 INDICATES A DEMISING PARTITION BY OTHERS. THE CONSTRUCTION OF THIS PARTITION MUST BE INCLUDED IN THIS SUBMITTAL. IF A FIRE RESISTANCE RATING IS REQUIRED FOR THE PARTITION, PLEASE INDICATE THE U.L. LISTING NUMBER FOR THAT PARTITION, AND PROVIDE A SEPARATE DETAIL ON THE DRAWING INDICATING THE REQUIRED PARTITION CONSTRUCTION.
7. SHEETS A1 AND A2; PLANS: A REFERENCE ON THESE SHEETS INDICATES 1/A2.1 (NEW EQUIPMENT LAYOUT). THERE IS NO SHEET A2.1. PLEASE REVISE.
8. SHEET A1; FLOOR PLAN: THE IBC TABLE 2902.1 REQUIRES A SERVICE SINK IN THIS TENANT SPACE. NO SERVICE SINK WAS LOCATED ON THE PLAN. PLEASE VERIFY.
9. SHEET A2; CEILING PLAN: AN EXIT SIGN IS NOT INDICATED AT THE EAST WALL EXIT. PLEASE PROVIDE.
10. SHEET A2; CEILING PLAN: THE PLAN DOES NOT INDICATE DIRECTIONAL EXIT SIGNAGE (AS REQUIRED BY SECTION 1011.1) FOR OCCUPANTS IN CORRIDOR 109. PLEASE PROVIDE.
11. SHEET A3; EQUIPMENT PLAN: PLEASE INDICATE ON THE PLAN THE POINT OF SALES COUNTERS AND THEIR APPROACHES SHALL MEET THE REQUIREMENTS OF THE ICC/ANSI SECTION 904.
12. SHEET A3; EQUIPMENT PLAN: PLEASE INDICATE ON THE PLAN THE RELOCATED SERVING COUNTERS (SEVERAL LOCATIONS) AND THEIR APPROACHES SHALL MEET THE REQUIREMENTS OF THE ICC/ANSI SECTION 904.
13. GENERAL: PLEASE PROVIDE A VALUATION (LABOR AND MATERIALS) FOR THIS PROJECT.
14. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/28/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/28/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for mercantile occupancy (e.g. a service sink).
2. The architectural plans indicate that a new sink is being installed as part of this activity. Provide a description of the proposed sink and verify that the fixture and faucet are 3rd-party listed. Reference: Section 303.4, IPC 2012.
3. Clarify the installation of the proposed sink: provide water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2012.
4. Provide the material standards for the water distribution piping materials and fittings. Reference: Sections 605.3 and 605.5, IPC 2012.
5. All water outlets or direct-connection of water to an appliance shall be protected against backflow (e.g. ice maker). Specify the device to be used for each outlet or appliance connection. Reference: Sections 608.15 and 608.16, IPC 2012.
6. Water supply connections to beverage dispensers (e.g. coffee, cappuccino, etc.) shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012.
03/28/2017 ROBERT SHERRY WATER REVIEW Reqs Change Revise the site plan to show the location and size of both the water meter and the reduced pressure backflow prevention assembly serving this address. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf.
03/28/2017 ERIC NEWCOMB ADA REVIEW Passed
03/28/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on drawing M1.0 to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
2. Provide calculations demonstrating adequate ventilation for the multiple zone recirculating HVAC system. Reference: Sections 403.2, 403.3, and 403.3.2.3, IMC 2012.
3. If the carbon dioxide storage consists of more than two 50-pound cylinders, provide a mechanical exhaust system activated by an asphyxiant gas detection system. Reference: Tucson Fire Department Standard Operating Guideline for Compressed Gases dated 04/28/2015.
04/07/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/19/2017 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/24/2017 MMENDIB1 OUT TO CUSTOMER Completed