Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM01917
Parcel: 13017149A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T17CM01917
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/20/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Non-residential occupancies require the supply of hot water (> 110 degrees Fahrenheit) for cleansing and building maintenance purposes. A water heater that delivers only a 20-degree temperature rise at 3-GPM will not meet this requirement unless the incoming water temperature is at least 90-degrees Fahrenheit. Reference: Section 607.1, IPC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/31/2017 KROBLES1 OUT TO CUSTOMER Completed