Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM01916
Parcel: 13017149A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM01916
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A3.0; Detail 16: There are two detail 16's indicated on this sheet. Please revise.
2. Previous comment 10; Sheet A3.0; Restroom signage: The revision of the signage indicates an incorrect lettering height (3/32"). Please revise per the ICC/ANSI Section 703.3.5.
05/03/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide a design for the roof access ladder and cage. Correct the keynote that appears to be pointing to the proposed ladder location. [Initial comment: Show how adequate access is being provided for the equipment located on the roof. Reference: Section 306.5, IMC 2012.]
05/03/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Termination of the excess pressure relief from the water heater over an elevated service sink is not approved location. Reference: Section 504.6 (6), IPC 2012. [Initial comment: Coordinate the specifications for fixture P-3 with the architect. P-3 is called out as a floor-level mop sink but on sheet A2.0 it is a 36"- high laundry tub. Reference: Section 107.2.1, IBC 2012.]