Permit Number: T17CM01914
Parcel: 13017149A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T17CM01914
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/20/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Non-residential occupancies require the supply of hot water (> 110 degrees Fahrenheit) for cleansing and building maintenance purposes. A water heater that delivers only a 20-degree temperature rise at 3-GPM will not meet this requirement unless the incoming water temperature is at least 90-degrees Fahrenheit. Reference: Section 607.1, IPC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/31/2017 KROBLES1 OUT TO CUSTOMER Completed