Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T17CM01912
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/20/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
10/20/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Non-residential occupancies require the supply of hot water (> 110 degrees Fahrenheit) for cleansing and building maintenance purposes. A water heater that delivers only a 20-degree temperature rise at 3-GPM will not meet this requirement unless the incoming water temperature is at least 90-degrees Fahrenheit. Reference: Section 607.1, IPC 2012. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/31/2017 | KROBLES1 | OUT TO CUSTOMER | Completed |