Permit Number: T17CM01912
Parcel: 13017149A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM01912
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A3.0; Detail 16: There are two detail 16's indicated on this sheet. Please revise.
2. Previous comment 10; Sheet A3.0; Restroom signage: The revision of the signage indicates an incorrect lettering height (3/32"). Please revise per the ICC/ANSI Section 703.3.5.
05/03/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide a design for the roof access ladder and cage. Correct the keynote that appears to be pointing to the proposed ladder location. [Initial comment: Show how adequate access is being provided for the equipment located on the roof. Reference: Section 306.5, IMC 2012.]
05/03/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Termination of the excess pressure relief from the water heater over an elevated service sink is not approved location. Reference: Section 504.6 (6), IPC 2012. [Initial comment: Coordinate the specifications for fixture P-3 with the architect. P-3 is called out as a floor-level mop sink but on sheet A2.0 it is a 36"- high laundry tub. Reference: Section 107.2.1, IBC 2012.]
2. Provide a switched luminaire for maintenance of the water heater located above the lay-in ceiling. Reference: Article 210.70C, NFPA 70-2011. [Initial comment: Clarify the location of the water heater and show how it is to be accessed for maintenance. Reference: Sections 501.4 and 502.5, IPC 2012.]