Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T17CM01912
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/03/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A3.0; Detail 16: There are two detail 16's indicated on this sheet. Please revise. 2. Previous comment 10; Sheet A3.0; Restroom signage: The revision of the signage indicates an incorrect lettering height (3/32"). Please revise per the ICC/ANSI Section 703.3.5. |
05/03/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide a design for the roof access ladder and cage. Correct the keynote that appears to be pointing to the proposed ladder location. [Initial comment: Show how adequate access is being provided for the equipment located on the roof. Reference: Section 306.5, IMC 2012.] |
05/03/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Termination of the excess pressure relief from the water heater over an elevated service sink is not approved location. Reference: Section 504.6 (6), IPC 2012. [Initial comment: Coordinate the specifications for fixture P-3 with the architect. P-3 is called out as a floor-level mop sink but on sheet A2.0 it is a 36"- high laundry tub. Reference: Section 107.2.1, IBC 2012.] 2. Provide a switched luminaire for maintenance of the water heater located above the lay-in ceiling. Reference: Article 210.70C, NFPA 70-2011. [Initial comment: Clarify the location of the water heater and show how it is to be accessed for maintenance. Reference: Sections 501.4 and 502.5, IPC 2012.] |