Permit Number: T17CM01821
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM01821
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/07/2017 ROBERT SHERRY WATER REVIEW Completed
03/07/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
03/07/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the proposed shampoo sinks are 3rd-party listed.
2. Revise the sanitary isometric to clearly show that the installation will comply with the plumbing code.
03/07/2017 ANDREW CONNOR ZONING REVIEW Approved
03/07/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide hating and cooling load calculations to justify the capacities of the proposed rooftop units.
2. Provide calculations to show that the space has adequate ventilation.
03/07/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/13/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Needs Review
03/13/2017 MARTIN BROWN FIRE REVIEW Approved
03/13/2017 GERRY KOZIOL WWM REVIEW Passed