Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM01821
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/07/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 03/07/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide hating and cooling load calculations to justify the capacities of the proposed rooftop units. 2. Provide calculations to show that the space has adequate ventilation. |
| 03/07/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Verify that the proposed shampoo sinks are 3rd-party listed. 2. Revise the sanitary isometric to clearly show that the installation will comply with the plumbing code. |
| 03/07/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 03/07/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/07/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/07/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/13/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/13/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 03/13/2017 | GERRY KOZIOL | WWM | REVIEW | Passed |