Permit Number: T17CM01820
Parcel: 11451216G

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM01820
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2017 ANDREW CONNOR ZONING REVIEW Approved
03/07/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide calculation to show that the expansion of the beauty parlor has adequate ventilation. Reference: Section 403.3, IMC 2012.
2. Provide exhaust for the new restroom; show how the exhaust fan will be controlled.
3. Provide balancing information. Reference: Section 403.7, IMC 2012.
03/07/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/07/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
03/07/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/07/2017 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide the size of the existing water meter and the reduced pressure backflow preventer serving the beauty parlor.
2. Provide the total water demand for the water meter serving the beauty parlor.
03/07/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide complete plumbing plans. Reference: Section 107.2.1, IBC 2012.
03/07/2017 MARTIN BROWN FIRE REVIEW Approved
03/07/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/21/2017 ARUIZ1 WWM REVIEW Needs Review