Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM01817
Parcel: 122170480

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM01817
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET g1.2; CODE ANALYSIS: PLEASE INDICATE ON THE DRAWINGS THE SQUARE FOOTAGE FOR EACH BUILDING.
2. SHEET g1.2; CODE ANALYSIS: THE ANALYSIS INDICATES A DRINKING FOUNTAIN IS REQUIRED AND PROVIDED. WHERE IS THIS LOCATED ON SHEET a1.0? IT MUST BE A HIGH/LOW DRINKING FOUNTAIN OR A SINGLE POINT OF USE WATER DISPENSER. PLEASE NOTE.
3. SHEET x1.1; RAMP PLAN: PLEASE INDICATE ON THIS PLAN THE ELEVATIONS OF THE SLAB AT THE DOOR AND AT THE BRICK WALKWAY.
4. SHEET x1.1; RAMP DETAIL 1: PLEASE INDICATE THE SLOPE OF THE RAMP ON THIS DETAIL (SEE IBC SECTION 1010).
5. SHEET x1.1; RAMP DETAIL 2: PLEASE INDICATE THE CROSS SLOPE OF THE RAMP ON THIS DETAIL (SEE IBC SECTION 1010).
6. SHEET x1.1; RAMP DETAIL 2: PLEASE INDICATE ON THIS DETAIL THE MAXIMUM AND MINIMUM DISTANCES FROM THE TOP OF THE RAMP SLAB TO THE ADJACENT GRADE (INDICATES 'VARIES').
7. SHEET a9.0; DETAIL 10: PLEASE INDICATE THE NUMBER AND SIZE OF CONNECTORS FOR METAL STUDS TO METAL STUDS.
8. SHEET a9.1; DETAIL 7: PLEASE INDICATE THE NUMBER AND SIZE OF CONNECTORS FOR METAL STUDS TO METAL STUDS.
9. SHEET p3.0; DETAIL 3: PLEASE EXTEND THE DETAIL UP TO INDICATE HOW THE ALL THREAD ROD THAT SUPPORTS THE NEW HOT WATER HEATER IS CONNECTED TO THE STRUCTURE ABOVE.
10. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/07/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/07/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE AWRITTEN RESPONSE.
#1. PROVIDE COMPLETE PANEL SCHEDULES FOR ALL THE PANELS AFFECTED PER THE SCOPE OF ELECTRICAL WORK THIS PROJECT.
#2. PROVIDE COMPLIANCE WITH THE 2012 IECC FOR THE INTERIOR LIGHTING.
REF: 2012 IBC 107.2.1, 2012 IECC, 2011 NEC.
03/07/2017 ROBERT SHERRY WATER REVIEW Completed
03/07/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/08/2017 LOREN MAKUS ENGINEERING REVIEW Approved
03/08/2017 ANDREW CONNOR ZONING REVIEW Approved
03/08/2017 JVINCEN1 FIRE REVIEW Approved
03/17/2017 GERRY KOZIOL WWM REVIEW Completed
03/17/2017 MMENDIB1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review