Permit Number: T17CM01782
Parcel: 117141030

Address:
340 S STONE AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM01782
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2017 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T17CM01782
Tenant Improvement (1st Review)
340 S Stone Avenue - HC-3 Zoning

TRANSMITTAL DATE: March 9, 2017

DUE DATE: April 4, 2017

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the proposed tenant improvements for "First Credit Union". While the proposed improvements do not impact the site improvements such as setbacks, parking, landscaping etc zoning cannot approve the TI plans at this time.

2. COMMENT: The property is Zoned HC-3 (Historic Overlay) and prior to any additional Zoning review or approval the plans must be reviewed by PDSD Historic Preservation Staff. The TI includes two changes proposed to the exterior walls that must be approved through the historic review process.

Change 1; is removal of an existing door facing Church Avenue and replacing it with a window.
Change 2; is removal of an existing window along the south-side of the building and reconstructing the area with a niche for a future ATM.

As mentioned, the changes do not affect any site requirements but due to the historic overlay a Historic review is required.

3. COMMENT: The applicant must contact Jonathan Mabry (Historic Preservation Officer) 837-6968 or Michael Taku (Lead Planner) 837-4963 for information related to the HPZ review. (Building elevation drawings may be required for this review.)


4. COMMENT: Once the HPZ review and approval process has been completed the plans must be reviewed by PDSD Zoning to ensure compliance with any of the HPZ conditions of approval, if any. The HPZ case number, date of approval and conditions of approval must be listed on the cover sheet as a general note. The HPZ case number must be listed next to the title block of all plan sheets.


5. COMMENT: Zoning is willing to review the building plans over the counter on the next submittal.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Tenant improvement plans and HPZ documentation
03/14/2017 MARTIN BROWN FIRE REVIEW Approved
03/21/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy (e.g. service sink and drinking fountain).
2. Water supply connections to beverage dispensers (e.g. coffee makers) shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012.
03/21/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Condensate drains may not terminate over a roof drain unless the roof drain terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
2. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
3. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2012.
03/21/2017 ROBERT SHERRY WATER REVIEW Completed
03/28/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET CS; BUILDING CODES: PLEASE ADD THE 2009 ICC/ANSI A117.1 ACCESSIBILITY CODE ON THIS SHEET.
2. SHEET CS; SYMBOLS LEGEND: THE WALL TYPE TAG REFERENCES SHEET A1.51. PLEASE REVISE THE REFERENCE.
3. SHEET CS; SYMBOLS LEGEND: THE INTERIOR ELEVATION TAG REFERENCES SHEET A4.2. PLEASE REVISE THE REFERENCE.
4. SHEET A1.1; SK1 AND SK2: A NOTE ON SK2 INDICATES THE LINTEL INDICATED IN SK1 CAN HAVE AN OPENING NO LARGER THAN 6'-4", WHILE NOTE 4 IN SK1 INDICATES AN OPENING NOT TO EXCEED 6'-0". PLEASE COORDINATE.
5. SHEET A1.13; GENERAL NOTES: PLEASE REVISE.
6. SHEET A6.01; WALL TYPE LEGEND: AT WALL TYPE 3.1, WHAT IS THE DOUBLE ASTERISK INDICATING?
7. SHEETS SP-1 THROUGH SP-5: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
8. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/04/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved