Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM01782
Parcel: 117141030

Address:
340 S STONE AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM01782
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2017 ANDREW CONNOR ZONING REVIEW Needs Review
03/06/2017 CLAYTON TREVILLYAN MECHANICAL-COMMERCIAL REVIEW Needs Review
03/06/2017 CLAYTON TREVILLYAN ELECTRICAL-COMMERCIAL REVIEW Needs Review
03/06/2017 DTAKAKI1 ENGINEERING REVIEW Approved
03/06/2017 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Needs Review
03/06/2017 CTREVIL1 WATER REVIEW Needs Review
03/06/2017 CLAYTON TREVILLYAN PLUMBING-COMMERCIAL REVIEW Needs Review
03/06/2017 CTREVIL1 FIRE REVIEW Needs Review
03/06/2017 CTREVIL1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/06/2017 CTREVIL1 WWM REVIEW Passed