Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE.
#1. INDICATE CONDUIT, WIRE, SIZES AND TYPES, FOR ALL CONDUITS, FEEDERS FOR THE SERVICE DISCONNECTS, CT CONDUITS.
#2. INDICATE TOTAL LOAD AND AIC RATINGS FOR SERVIVE EQUIPMENT.
#3. GROUNDING SHOULD INCLUDE WATER AND GAS, BUILDING STEEL IF APPLICABLE AS REQUIRED PER 250 NEC.
REF: CITY OF TUCSON COMMERCIAL PLAN SUBMITTAL REQUIREMENTS, 2011 NEC.
03/06/2017 ANDREW CONNOR ZONING REVIEW Approved