Review Details: COMMERCIAL - TI

Permit Number - T17CM01771
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/06/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/06/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/06/2017 ROBERT SHERRY WATER REVIEW Completed
03/06/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET a0.2; EXITING PLAN: SHEET a0.1 INDICATES 144 TOTAL OCCUPANTS, WHILE THE THREE EXITS ON THE PLAN ON SHEET a0.2 INDICATE 137 OCCUPANTS (83 + 46 + 8). PLEASE COORDINATE.
2. SHEET a3.0; FLOOR PLAN KEY NOTES: NOTE 44 INDICATES ROOF MOUNTED EQUIPMENT AND NEW CURBS AND OPENINGS. PLEASE PROVIDE A ROOF PLAN AND INDICATE THESE ITEMS. INDICATE THE WEIGHT OF NEW EQUIPMENT/UNITS, AND PROVIDE STRUCTURAL CALCULATIONS AS REQUIRED FOR ADEQUACY OF THE EXISTING ROOF SYSTEM TO SUPPORT THE NEW LOADS.
3. SHEET a3.0; FLOOR PLAN KEY NOTES: NOTE 45 INDICATES "PANIC HARDWARE PROVIDE IF NOT ALREADY INSTALLED'. PLEASE FIELD VERIFY AND INDICATE IN THIS NOTE IF PANIC HARDWARE IS EXISTING OR NEEDS TO BE ADDED.
4. SHEET a9.0; DETAIL 15: PLEASE ADD THE LENGTH OF THE VERTICAL GRAB BAR ON THE DETAIL.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/06/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Clarify the natural gas piping - is it new or existing? The pressure is noted as being greater than 2 PSI and the IFGC sizing table used is not specified.
03/07/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
03/07/2017 ANDREW CONNOR ZONING REVIEW Approved
03/07/2017 MARTIN BROWN FIRE REVIEW Approved
03/10/2017 GERRY KOZIOL WWM REVIEW Needs Review