Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM01718
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/16/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Water supply connections to beverage dispensers shall be protected with backflow preventers conforming to ASSE 1022 (the Watts LF7 dual check is listed to ASSE 1024). Reference: Section 608.16.1, IPC 2012. 2. The steam table, K9, is identified as being gas-fired. Determine the gas input and supply gas to the appliance. |
| 03/16/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. If the carbon dioxide storage consists of more than two 50-pound cylinders, provide a mechanical exhaust system activated by an asphyxiant gas detection system. Reference: Tucson Fire Department Standard Operating Guideline for Compressed Gases dated 04/28/2015. 2. Revise the exhaust duct fire wrap detail to indicate that the field-applied grease duct enclosure must continuously enclose all sides of the grease duct from the duct origin to the duct termination. Reference: Section 506.3.11.2, IMC 2012. 3. Verify that the distance between EF-1 and the parapet wall is at least 2-feet from the parapet wall and the discharge shall be at least as high as the parapet but not less than 40" above the roof surface. Reference: sections 506.3.3.13 and 506.5.5, IMC 2012. 4. Provide 18" of clearance from the Type 1 grease hood to combustibles (e.g. the wall of the walk-in cooler). Reference: Section 507.9, IMC 2012. 5. Provide a Type II hood over the gas-fired steam table. Reference: Section 507.2.2, IMC 2012. |
| 03/29/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |