Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM01685
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/03/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. A "fully programmable" thermostat may not have the capability of automatically adjusting the start time of the HVAC equipment. Provide a statement requiring this capability. [Second comment: Comment not addressed.] [Initial comment: Verify that the specified HVAC systems are provided with controls that are capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy. Reference: Section C403.2.4.3.3, IECC 2012.] 2. A barometric relief damper located adjacent to the outside air damper does not ensure that there will be no recirculation of relief air. [Second comment: Comment not addressed.] [Initial comment: Clarify how excess outside air relief from the building is to be accomplished without recirculation. Reference: Section C403.3.1.1.4, IECC 2012.] |
04/03/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed |