Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM01685
Parcel: 13613001T

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM01685
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. A "fully programmable" thermostat may not have the capability of automatically adjusting the start time of the HVAC equipment. Provide a statement requiring this capability. [Second comment: Comment not addressed.] [Initial comment: Verify that the specified HVAC systems are provided with controls that are capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy. Reference: Section C403.2.4.3.3, IECC 2012.]
2. A barometric relief damper located adjacent to the outside air damper does not ensure that there will be no recirculation of relief air. [Second comment: Comment not addressed.] [Initial comment: Clarify how excess outside air relief from the building is to be accomplished without recirculation. Reference: Section C403.3.1.1.4, IECC 2012.]
04/03/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2017 MMENDIB1 OUT TO CUSTOMER Completed