Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM01677
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/27/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A00.00; APPLICABLE CODES: PLEASE REVISE THE ICC A117.1 TO THE 2009 EDITION, AND REMOVE THE 2010 ADA. 2. SHEET A00.00; DRAWING INDEX: THE INDEX INDICATES 7 COMPANION SHEETS FOR THE ATM KIOSK, BUT THERE ARE ACTUALLY 45 SHEETS. PLEASE CLARIFY. 3. SHEET A00.50; SHEET NOTES: NOTE B REFERENCES SHEET A00.10 FOR REFLECTED CEILING NOTES. PLEASE REVISE. 4. SHEET 34 OF 45; SPECIAL INSPECTION STATEMENT: THE IBC REFERENCES FOR STEEL, CONCRETE, AND SOILS TABLES SHOULD BE REVISED TO THE 2012 EDITION OF THE IBC. 5. SHEET 35 OF 45; NOTES: NOTE 2 INDICATES 'FOUNDATION BY OTHERS', BUT THE FOUNDATION CALCULATIONS AND DRAWINGS BY THE SAME CIVIL ENGINEER ARE INCLUDED IN THIS SUBMITTAL. PLEASE CLARIFY. 6. SHEET 35 OF 45; NOTES: NOTE 5 INDICATES THE ATM TUBES SHOULD BE SIZED BY A STRUCTURAL ENGINEER, BUT THOSE WERE SIZED IN THE STRUCTURAL CALCULATIONS BY THE SAME CIVIL ENGINEER IN THIS SUBMITTAL. PLEASE CLARIFY. 7. SHEET 35 OF 45; NOTES: NOTE 7 WAS NOT LOCATED ON THE PLAN. PLEASE VERIFY. 8. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
03/27/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE. #1. REF: PLAN SHEET E-3. THE FEEDERS FOR THE NEW PANELS AT THE ATM LOCATIONS SHOW ONLY TWO #6 CONDUCTORS AND GROUNDS, PLEASE INCLUDE A THIRD CONDUCTOR AS REQUIRED FOR A 3 WIRE SYSTEM PER PANEL SCHDULES, 120/240V SESTEM. ( 2-PHASE, 1-NEUTRAL, + GROUNDS ). #2. PROVIDE FOR GROUNDING ELECTRODE SYSTEMS TO BE INSTALLED AT THE ATM KIOSKS AS REQUIRED PER NEC 250.32. REF: 2012 IBC SEC. 107.2.1, 2011 NEC. |