Permit Number: T17CM01593
Parcel: 130051130

Address:
1810 S AMALIA AV

Review Status: Active

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T17CM01593
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2017 ANY NPPO REVIEW Active
02/28/2017 ANY ENGINEERING REVIEW Active
02/28/2017 ANY BUILDING-RESIDENTIAL REVIEW Active
06/27/2017 ANDREW CONNOR ZONING REVIEW Reqs Change COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

The applicant has 2- 9' tall-detached storage units. The proposed side-yard setbacks is 3' 7" and 4' 2" to the South. The site has a pending Notice of Violation Case # T17DV00403.