Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T17CM01579
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/22/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/27/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE. #1. THE SHEET INDEX ON THE COVER SHEET DOES NOT SEEM TO CORRELATE WITH THE INDIVIDUAL DRAWINGS. For example, the SHEET INDEX describes plan sheet PV 2.2 as 3-line diagram, however PV2.2 seems to be a different PV array? Plan sheet PV 2.0 is not shown on the sheet index? Etc. Ref: 2012 IBC 107.2.1, 2011 NEC |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/28/2017 | KROBLES1 | OUT TO CUSTOMER | Completed |