Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM01481
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/23/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 02/23/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 02/23/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A2.0; FLOOR PLAN KEYNOTES: ON KEYNOTE 10, PLEASE ADD A REFERENCE TO DETAIL 1/A2.0. 2. SHEET A2.0; WALL TYPES: PLEASE INDICATE THE WALL STUD GAUGE ON THE WALL TYPE A DETAIL. 3. SHEET A4.0; DETAIL 4: PLEASE INDICATE KEYNOTE 9 ON THE DETAIL. 4. SHEET A4.0; DETAIL 5: WHERE IS THIS DETAIL INDICATED OR REFERENCED ON THE PLAN? PLEASE VERIFY. 5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 02/24/2017 | MARTIN BROWN | FIRE | REVIEW | Approved |