Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM01439
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/22/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
02/22/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.6.5, IMC 2012. |
02/22/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/22/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
02/22/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. GENERAL: PLEASE ADD A DATE TO ALL OF THE PROFESSIONAL SEALS. |
02/22/2017 | ROBERT SHERRY | WATER | REVIEW | Passed | |
02/22/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2012. |
02/22/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/24/2017 | LBOJORQ1 | FIRE | REVIEW | Needs Review | |
02/24/2017 | LBOJORQ1 | WWM | REVIEW | Needs Review |