Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM01431
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM01431
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2017 KEN BROUILLETTE FIRE REVIEW Approved
03/02/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that an automatic faucet will be provided for the relocated lavatory. The faucet shall dispense a maximum of 0.25 gallons per metering cycle and each cycle will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Appliances (e.g. soda dispensers, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
3. Water supply connections to beverage dispensers shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012.
4. Verify that separate indirect waste pipes will be provided for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
03/02/2017 ROBERT SHERRY WATER REVIEW Completed
03/02/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.2.2, IMC 2012.
03/14/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G-001; SITE INFORMATION/OCCUPANCY: THE TYPE OF OCCUPANCY INDICATES "B (UNDER 50 OCCUPANTS)". PLEASE REVISE THIS TO INDICATE AN A-2 OCCUPANCY CLASSIFICATION (PER THE IBC SECTION 303.1.1, FOR OCCUPANT LOAD OF LESS THAN 50, AN ASSEMBLY OCCUPANCY CLASSIFICATION MAY BE CLASSIFIED AS A 'B').
2. SHEET G-005; TOTAL SQUARE FOOTAGE: PLEASE PROVIDE THE TOTAL SQUARE FOOTAGE ON THIS SHEET FOR THE EXTERIOR AND INTERIOR (INDICATES X,XXX).
3. SHEET I-411; DETAILS 7 AND 12: PLEASE ADD THE VERTICAL GRAB BAR PER THE ICC/ANSI FIGURE 604.5.1.
4. SHEET I-502; DETAIL 5 AND ANUMEAL ELEVATIONS/DETAILS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
5. SHEET I-503; DETAILS 8 AND 10: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
6. SHEET I-504; DETAILS 7, 9, AND 13: PLEASE PROVIDE THE DIAGONAL BRACE SIZE.
7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/20/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE.
#1. ALL PLANS ARE TO SEALED AND SIGNED BY A ELECTRICAL ENGINEER REGISTERED IN THE STATE OF ARIZONA.
#2. REF: PLAN SHEET E2.3 AND E6.0. MINIMUM LETTERING FONT SIZE IS 3/32 OF AN INCH.
REF: CITY OF TUCSON COMMERCIAL PLAN SUBMITTAL REQUIREMENTS, 2012 IBC SEC. 107.2.1, 2011 NEC.
03/21/2017 GERRY KOZIOL WWM REVIEW Reqs Change NEEDS IWC REVIEW PER GERRY KOZIOL.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/04/2017 MMENDIB1 OUT TO CUSTOMER Completed