Permit Number: T17CM01384
Parcel: 13502134K

Address:
7050 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM01384
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2017 KEN BROUILLETTE FIRE REVIEW Approved
02/28/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Appliances (e.g. coffee brewers, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Note: water supply connections to beverage dispensers shall be protected with backflow preventers conforming to ASSE 1022. Reference: Sections 608.1, 608.3, and 608.16.1, IPC 2012.
02/28/2017 ROBERT SHERRY WATER REVIEW Completed
02/28/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/08/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change T17CM01384
TI: FRY'S MARKET
1. SHEET AD2.2; DEMOLITION KEYNOTES AND GENERAL NOTE: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
2. SHEET AD2.2; DEMOLITION KEYNOTES: NOTE 4 REFERENCES SHEET A1.2 FOR THE REFLECTED CEILING PLAN. PLEASE REVISE THE REFERENCE.
3. SHEET A1.1; FLOOR PLAN: THE REFERENCE FOR THE ENLARGED DAIRY FLOOR PLAN INDICATES D/A4.2. PLEASE REVISE.
4. SHEET A1.1; FLOOR PLAN: THE REFERENCE FOR THE ENLARGED MEAT/SEAFOOD PLAN INDICATES F/A4.2. PLEASE REVISE.
5. SHEET A4.1; PLAN E: PLEASE VERIFY IN THE APPROPRIATE KEYNOTES THE CHECKSTANDS MEET THE ACCESSIBILITY REQUIREMENTS OF THE ICC/ANSI SECTION 904.4.
6. SHEET A5.2; WALL TYPES C AND F: AT THE DIAGONAL WALL BRACING, PLEASE INDICATE THE BRACING SIZE, SPACING, AND NUMBER AND SIZE OF CONNECTORS OF THE BRACE TO THE WALL AND TO THE STRUCTURE ABOVE. ADD DETAILS AS REQUIRED INDICATING THE CONNECTION TO THE STRUCTURE ABOVE. REMOVE THE NOTES "AS REQUIRED" AND "AS NEEDED".
7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/14/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
03/17/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE CORRECT THE NOTE THAT REFERENCES THE STARBUCKS TO PLAN SHEET E1.1 ON THE ELECTRICAL POWER PLAN E2.1.
03/21/2017 GERRY KOZIOL WWM REVIEW Approved