Permit Number: T17CM01297
Parcel: 13405118R

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T17CM01297
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. With regard to the COMcheck Envelope Compliance Certificate, show how a continuous layer of insulation (R-2) is to be installed on the roof assembly. Reference: Section 303.2, IECC 2012.
2. The COMcheck Envelope Compliance Certificate calls out R-24 cavity insulation in the exterior walls along with R-2 continuous insulation. The exterior wall sections on A5.1 show R-19 cavity insulation and do not specify the R-value for the continuous insulation (see Specification Section 07240-2D on sheet A6). Reference: Section C103.2, IECC 2012.
3. Coordinate the window specifications (Section 08800, A6) with the window descriptions used on COMcheck. Note that the fenestration shall be NFRC -certified for U-value and the Solar Heat Gain Coefficient. Reference: Sections C103.2 and C303.1.3, IECC 2012.
4. Specify the U-value and the Solar Heat Gain Coefficient for the glazed door on the drawings and coordinate the values with COMcheck. Reference: Sections C103.2 and C303.1.3, IECC 2012.
5. Verify that the relief air outlet on the specified rooftop heat pumps is not located in a way that would allow recirculation of the relief air into the building. Reference: section C403.3.1.1.4, IECC 2012.
03/03/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the civil drawings referenced on sheet P1 that show the location, route and size of the proposed building sewer, the locations of the cleanouts, and the point of connection to the public sewer. Reference: Section 107.2.1, IBC 2012.
2. Clarify the size of the proposed reduced pressure backflow preventer; it is shown as 2" in the water calculations and 1-1/2" in General Note B on sheet P1.
03/03/2017 ROBERT SHERRY WATER REVIEW Reqs Change Provide the civil drawings referenced on sheet P1 that show the location and sizes of the proposed water meter, backflow preventer, and water service to the building. Reference: Section 107.2.1, IBC 2012.
03/14/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1; PLAN KEY NOTES: NOTES 4, 9, AND 10 WERE NOT LOCATED ON THE PLAN. PLEASE VERIFY.
2. SHEET A1; WALL TYPES: ON WALL TYPES A AND A1, PLEASE PROVIDE THE STUD GAUGE, OR REFERENCE STRUCTURAL (VERIFY STRUCTURAL PROVIDES THAT INFORMATION).
3. SHEET A2; PLAN KEY NOTES: NOTE 2 WAS NOT LOCATED ON THE PLAN. PLEASE VERIFY.
4. SHEET A3; SECTIONS 5 AND 6: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
5. SHEET A3; SECTION NOTES: THERE ARE MANY SECTION NOTES THAT ARE NOT INDICATED ON THE SECTIONS. PLEASE PROVIDE.
6. SHEET A5.1; SECTION NOTES: NOTES 6, 8, 10, 11, 13, AND 18 WERE NOT LOCATED ON THE SECTIONS. PLEASE VERIFY.
7. SHEET S3.0; ROOF FRAMING PLAN NOTES: NOTE 6 (LOCATED ON THE PLAN NEAR GRIDS C AND 1) DOES NOT APPEAR TO BE CORRECT. PLEASE VERIFY.
8. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/20/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
03/21/2017 KROBLES1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2017 KROBLES1 OUT TO CUSTOMER Completed