Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/30/2017 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T17CM01284 - PLAN REVIEW COMMENTS 2 Reviewer: Chris Anderson, March 29, 2017 BUILDING – COMMERCIAL Sheet GI001 must be sealed by the Architect. In line with previous note 23, add note under sliding doors elevations “Horizontal sliding egress doors shall meet all criteria of 2012 IBC 1008.1.4.3 including being capable of being manually operated in the event of power failure.” |
03/30/2017 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | MECHANICAL – COMMERCIAL Per previous mechanical comment 2, submit heating and cooling load calculations to justify the capacity of the selected heating and cooling equipment. No load calculations were included with first resubmittal. Per previous mechanical comment 2, submit COMcheck for heating and cooling equipment. No COMcheck was included with first resubmittal. |
03/30/2017 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | ELECTRICAL – COMMERCIAL Regarding previous electrical comment 3, the site photometric chart provided in resubmittal 1 is not information in a form that shows compliance with Outdoor Lighting Code Table 401.1. Please provide outdoor lumen calculations per the Table, showing lumens per fixture type x number of each type of fixture, and with total lumens vs total lumens allowed and total unshielded lumens vs total unshielded lumens allowed. Regarding previous electrical comment 5 and response, no electrical COMcheck was included with resubmittal. |
03/30/2017 | FRODRIG2 | WATER | REVIEW | Reqs Change | WATER – COMMERCIAL Per previous water comment 1, “provide water calculations to justify new 2” water meter and service line.” No change has been made to plumbing plans. Per previous water comment 2, “on sheet P101 water appears to enter the building from the north side; however the civil utility plan shows that it enters from the west side. Revise civil utility sheet.” No change has been made to either the plumbing plans or civil utility sheet. |
03/30/2017 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | PLUMBING – COMMERCIAL Regarding previous plumbing comment 1 and response, submit evidence that the Zurn Z812A4-XL-FC will dispense no more than 0.25 gallon per metering cycle. |
04/07/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/07/2017 | DAVID RIVERA | ZONING | REVIEW | Approved | |
04/07/2017 | FRODRIG2 | WWM | REVIEW | Approved |