Permit Number: T17CM01284
Parcel: 114469380

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM01284
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T17CM01284 - PLAN REVIEW COMMENTS 2
Reviewer: Chris Anderson, March 29, 2017
BUILDING – COMMERCIAL
Sheet GI001 must be sealed by the Architect.
In line with previous note 23, add note under sliding doors elevations “Horizontal sliding egress doors shall meet all criteria of 2012 IBC 1008.1.4.3 including being capable of being manually operated in the event of power failure.”
03/30/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – COMMERCIAL
Per previous mechanical comment 2, submit heating and cooling load calculations to justify the capacity of the selected heating and cooling equipment. No load calculations were included with first resubmittal.
Per previous mechanical comment 2, submit COMcheck for heating and cooling equipment. No COMcheck was included with first resubmittal.
03/30/2017 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL – COMMERCIAL
Regarding previous electrical comment 3, the site photometric chart provided in resubmittal 1 is not information in a form that shows compliance with Outdoor Lighting Code Table 401.1. Please provide outdoor lumen calculations per the Table, showing lumens per fixture type x number of each type of fixture, and with total lumens vs total lumens allowed and total unshielded lumens vs total unshielded lumens allowed.
Regarding previous electrical comment 5 and response, no electrical COMcheck was included with resubmittal.
03/30/2017 FRODRIG2 WATER REVIEW Reqs Change WATER – COMMERCIAL
Per previous water comment 1, “provide water calculations to justify new 2” water meter and service line.” No change has been made to plumbing plans.
Per previous water comment 2, “on sheet P101 water appears to enter the building from the north side; however the civil utility plan shows that it enters from the west side. Revise civil utility sheet.” No change has been made to either the plumbing plans or civil utility sheet.
03/30/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
Regarding previous plumbing comment 1 and response, submit evidence that the Zurn Z812A4-XL-FC will dispense no more than 0.25 gallon per metering cycle.
04/07/2017 MARTIN BROWN FIRE REVIEW Approved
04/07/2017 DAVID RIVERA ZONING REVIEW Approved
04/07/2017 FRODRIG2 WWM REVIEW Approved