Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM01271
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/23/2017 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/23/2017 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | It appears the occupant load sheet C-1 has been calculated incorrectly. Please refer to table 1004.1.2 of the 2012 International Fire Code. Exercise rooms should be calculated at 50 gross. Please revise and indicate on plan. If the occupant load is greater than 50, panic hardware is required. Please refer to section 1008.1.10 for guidance. |
| 03/01/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed and that a notation shall be placed beneath the seal, written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). 2. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy (e.g. service sink). 3. The architectural floor plan on A-2 shows what appear to be a high-low drinking fountain located on the north wall of the new men's shower room. Specify the drinking fountain and show how it is to be installed. Reference: Section 107.2.1, IBC 2012. 4. Provide fixture descriptions more precise than "Kohler" so that the listing information and installation requirements for each fixture can be reviewed. Reference: Section 107.2.1, IBC 2012. 5. Specify the shower controls and fittings. Reference: Section 424, IPC 2012. 6. Provide details showing how the shower enclosures and the floor of the showers are to be constructed in accordance with the requirements of 417, IPC 2012. 7. Provide automatic faucets for the lavatories that will dispense a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 8. Provide a detail showing that the water heater located above the ceiling will have adequate access and maintenance space. Reference: Section 502.3, IPC 2012 and Article 210.70(c), NEC 2011. 9. In non-residential occupancies, the plumbing code requires hot or tempered water to be available for bathing and washing purposes. Show that you will have adequate hot or tempered water available for the two showers considering that you are installing a 20-gallon water heater with a recovery of 12-gallons per hour and a storage temperature of 120 degrees Fahrenheit. Reference: Section 607.1, IPC 2012. |
| 03/01/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide calculations demonstrating that there is adequate ventilation for the proposed occupancy of the suite. Reference: Sections 403.2 and 403.3, IMC 2012. 2. Provide the balancing data for the restroom exhaust fans. If the HVAC system supplies air into the restrooms, provide the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4) and 403.3, IMC 2012. |
| 03/01/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/06/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T17CM01271 CROSSFIT 646 TI 1. SHEET C-1; DEVELOPMENT DATA: THE OCCUPANCY TYPE IS LISTED AS A-3 (GYMNASIUM), BUT THE OCCUPANT LOAD IS CALCULATED USING A FACTOR OF 200 SF/PERSON. PLEASE CLARIFY WHERE THE 200 SF/PERSON IS ALLOWED FROM THE IBC TABLE 1004.1.2. 2. SHEET C-1; APPLICABLE CODES: AT THE END OF THE 2012 IBC CODE, THE DRAWING REFERENCES THE IRC (IN PARENTHESES). PLEASE REVISE. 3. SHEET C-1; DEVELOPMENT DATA: WHAT WAS THE PREVIOUS OCCUPANCY TYPE IN THIS TENANT SPACE? PLEASE INDICATE ON THE DRAWINGS. 4. SHEET A-2; ADA TOILET PLAN: FOR THE CLEAR FLOOR SPACE ON THE PULL SIDE OF THE DOOR, INDICATE THE MANEUVERING CLEARANCE USING THE ICC/ANSI FIGURE 404.2.3.2(a). 5. SHEET A-2; ADA TOILET PLAN: FOR THE CLEAR FLOOR SPACE ON THE PUSH SIDE OF THE DOOR, INDICATE THE MANEUVERING CLEARANCE USING THE ICC/ANSI FIGURE 404.2.3.2(b). 6. SHEET A-2; SHOWER CONTROL WALL: PLEASE REVISE THE GRAB BARS ON THE DRAWING FOR THE TRANSFER TYPE SHOWER PER THE ICC/ANSI FIGURE 608.3.1, INCLUDING HORIZONTAL GRAB BARS ON THE CONTROL WALL AND THE BACK WALL (SECTION 608.3.1.1), AND A VERTICAL GRAB BAR ON THE CONTROL WALL (SECTION 608.3.1.2). 7. SHEET A-2; SHOWER CONTROL WALL: PLEASE REVISE THE CONTROL AREA ON THE DRAWING FOR THE TRANSFER TYPE SHOWER PER THE ICC/ANSI FIGURE 608.4.1. 8. SHEET A-2 (FLOOR PLAN); SHEET A-2 (TYPICAL INTERIOR PARTITION DETAIL): THE WALL FILL-IN AREA IN THE WOMEN'S SHOWER WOULD MOST LIKELY REQUIRE 6" METAL STUDS TO MATCH THE EXISTING PLUMBING WALL STUDS. SHOULD SECTION 3/A-2 BE REVISED? PLEASE VERIFY. 9. SHEET A-2; TYPICAL INTERIOR PARTITION DETAIL: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES. 10. SHEET A-2; TYPICAL INTERIOR PARTITION DETAIL: PLEASE INDICATE THE STUD BRACING SIZE AND ADD THE NUMBER AND SIZE OF CONNECTORS TO THE BRACE AT THE TOP OF THE PARTION AND TO THE STRUCTURE ABOVE. 11. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/08/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 03/17/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/22/2017 | FRODRIG2 | WWM | REVIEW | Approved |