Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM01216
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM01216
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2017 ANDREW CONNOR ZONING REVIEW Approved
02/14/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide exhaust for the fitting rooms. Reference: Section 403.3, IMC 2012.
2. Explain how not installing an economizer based on exception 4 (low operating hours) of Section C403.3.1, IECC 2012 is applicable to this activity. Low operating hours for a system is defined as operating less than 20 hours per week.
02/14/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/14/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
02/14/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET a101; KEYNOTE 2: PLEASE INDICATE ON THE KEYNOTE THE SALES COUNTERS MUST MEET THE REQUIREMENTS OF THE ICC/ANSI SECTION 904 FOR ACCESSIBLE APPROACH AND HEIGHT.
2. SHEET a103; DETAIL 3: PLEASE INDICATE IN THE TITLE THAT THIS IS PARTITION TYPE A (IT IS REFERENCED IN DETAIL 2).
02/14/2017 ROBERT SHERRY WATER REVIEW Completed
02/14/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/14/2017 MARTIN BROWN FIRE REVIEW Approved
02/14/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed