Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM01216
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/14/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
02/14/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide exhaust for the fitting rooms. Reference: Section 403.3, IMC 2012. 2. Explain how not installing an economizer based on exception 4 (low operating hours) of Section C403.3.1, IECC 2012 is applicable to this activity. Low operating hours for a system is defined as operating less than 20 hours per week. |
02/14/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/14/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
02/14/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET a101; KEYNOTE 2: PLEASE INDICATE ON THE KEYNOTE THE SALES COUNTERS MUST MEET THE REQUIREMENTS OF THE ICC/ANSI SECTION 904 FOR ACCESSIBLE APPROACH AND HEIGHT. 2. SHEET a103; DETAIL 3: PLEASE INDICATE IN THE TITLE THAT THIS IS PARTITION TYPE A (IT IS REFERENCED IN DETAIL 2). |
02/14/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
02/14/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
02/14/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
02/14/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |