Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM01203
Parcel: 11720016G

Address:
110 S CHURCH AV

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T17CM01203
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2017 KEN BROUILLETTE FIRE REVIEW Reqs Change Per the IFC 2012 Edition, section 503.1.1 an approved fire apparatus road needs to be provided to within 150 feet of all portions of the proposed exterior walls. The road needs to be a minimum 20 feet wide and a fire department turnaround may be needed.
03/28/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The area drain located near column A-10 (sheet P1.3F) starts out with a 4" drain line and then transitions to a 3" RWL. The size of a drainage pipe shall not decrease in the direction of flow. Reference: Section 1101.5, IPC 2012.
03/28/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/28/2017 ROBERT SHERRY WATER REVIEW Passed
03/30/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: La Placita - Foundation Only
T17CM01203
Foundation Plan (1st Review)

TRANSMITTAL DATE: March 30, 2017

1. The foundation plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. It appears that the foundation plan matches the proposed development package DP17-0038 but until the development package has been approved Zoning cannot approve the foundation plan.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
04/05/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change T17CM01203
La Placita Apartment Homes Foundation Only Permit

1. Sheets A0.1 through A1.5F: These sheets were used for general reference only. A full review of the content indicated on these sheets will be made during a later review.
2. Sheet S1.0-F; Design Loads: The live loads indicated on this sheet are roof (20 PSF reducible), garage floor (40 PSF non-reducible), apartment floor (40 PSF reducible), and stair (100 PSF). Per the architectural plans (sheets A0.2 through A0.6), and the IBC Table 1607.1, please list on the drawings required design live loads for office floors and lobbies (Level 1), residential corridors and lobbies serving private rooms and public rooms (Levels 1 through 6), assembly areas (Level 2), and the pool/spa area (Level 6). Please verify these loads are included in the building design.
3. Sheet s1.0-F; Design Criteria (Foundations): The first note indicates an allowable soil bearing value of 7000 PSF for existing basement wall footings. Please verify where this value was indicated in the geotechnical report.
4. Sheet S2.0-F (Foundation Plan); Structural Calculations (Page 7): The structural calculations indicate wall W2 is the same design as wall W1. However, the foundation plan (and the wall schedule on sheet S1.5-F) indicate a different wall thickness and reinforcing. Please verify.
5. Sheet S2.0-F (Foundation Plan); Structural Calculations (Page 8): The structural calculations indicate wall W3 is the same design as wall W1. However, the foundation plan (and the wall schedule on sheet S1.5-F) indicate a different wall thickness and reinforcing. Please verify.
6. Sheet S2.0-F (Foundation Plan); Structural Calculations (Page 6): The structural calculations indicate wall W6 at the elevators, with the footing calculations on page 22. However, the structural calculations for the stair footings (adjacent to the elevators) were not located (footings F11 and F19 are different from the elevator footings). Please verify and indicate the stair footing design calculations.
7. Structural calculations: Please include in the structural calculations key plans for each building level, indicating the framing layout (do not require member sizes). These will be used in the coordination with the spread footing and columns key plan on Page 55 of the calculations (individual member designs for the framing are not required).
8. Structural calculations; Page 6: In the structural calculations, the wall between Grids D and F (approximately) and on Grid 0.1 (approximately) is denoted as RW2. Is this ERW2? Please verify.
9. General: Please include in the calculations key plans for each building level (including the roof) indicating the design live loads and the areas those loads are applicable. Include mechanical loads as required.
10. Structural calculations and foundation plans: Please verify the revisions to the building live loads (per comment 2) are applied to the design structural calculations as required, and changes to any members are included in the calculations for the foundation design.
11. General: Please provide written responses to all review comments.
04/07/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/10/2017 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change Requires approval of DP17-0038 prior to approval.
04/11/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/13/2017 GERRY KOZIOL WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/18/2017 MMENDIB1 OUT TO CUSTOMER Completed