Permit Number: T17CM01124
Parcel: 10714007A

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T17CM01124
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2017 KEN BROUILLETTE FIRE REVIEW Approved
02/16/2017 STEVE SHIELDS ZONING REVIEW Approved
02/17/2017 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Approved
02/22/2017 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Reqs Change A note shown on sheets A-3, A-4, and A-5 states that "structural analysis is being performed by others." In addition, the submitted structural calculations note that the foundation of the guyed-tower was not analyzed to determine if it was adequate for the modifications to the tower. Complete the structural analysis of the tower to determine if the existing tower and foundation have adequate capacity for the proposed modifications.
02/24/2017 FRODRIG2 COMMUNICATIONS REVIEW Approved LETTER SENT TO RECORDS
03/14/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2017 LBOJORQ1 OUT TO CUSTOMER Completed