Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T17CM01053
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/05/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/05/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 04/05/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Verify that the configuration of the economizer barometric damper for the specified packaged heat pump will not result in recirculation of the relief air into the building. Reference: Section C403.3.1.1.4, IECC 2012. [Initial comment: Clarify how excess outside air relief from the building is to be accomplished during economizer operation. Reference: Section C403.3.1.1.4, IECC 2012.] |
| 04/17/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |