Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM01053
Parcel: 137055220

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM01053
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2017 MARTIN BROWN FIRE REVIEW Reqs Change Occupant load dictates two exits. International Fire Code prohibits exiting from a lesser hazard through a greater hazard (section 1014.2), therefore the rear exit cannot be utilized as a second exit. Please indicate how compliance will be achieved.
02/23/2017 ROBERT SHERRY WATER REVIEW Completed
02/24/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the size of the new horizontal drain serving the new mop sink and the new drinking fountain; it is shown as 3" in detail 5/M3.0 (keynote #4) but is shown as 4" in the riser diagram, 7/M3.0. Reference: Section 107.2.1, IBC 2012.
2. Clarify the keynotes used in the riser diagrams (e.g. #2 and #3 in 7/M3.0 and #4 and #9 in 8/M3.0). Reference: Section 107.2.1, IBC 2012.
3. Correct the note calling for a vacuum breaker on the cold water supply to the water heater (detail 3/M3.0); it is supposed to be a vacuum relief valve. Reference: Section 504.2, IPC 2012.
02/24/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on the drawings to a minimum height of 3/32-inch (e.g. 1/M1.0 and 2/M2.0). Reference: Section 107.2.1, IBC 2012.
2. Where is keynote 10 on the mechanical plan, 1/M1.0, described? Reference: section 107.2.1, IBC 2012.
3. Clarify how excess outside air relief from the building is to be accomplished during economizer operation. Reference: Section C403.3.1.1.4, IECC 2012.
4. Detail 5/M2.0 calls for the condensate drains from the heat pumps to terminate over a roof drain. Condensate drains may not terminate over a roof drain unless the roof drain terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Similarly, note #4 of the packaged heat pump schedule, detail 2/M2.0, states that the condensate drains are to terminate over a splash block on the roof. Condensate drains shall terminate in an approved location, as listed in Section 307.2.1, IMC 2012, as amended by the City of Tucson.
5. Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012 and C403.2.5, IECC 2012.
6. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012.
03/01/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change T17CM01053
FOOT LOCKER TENANT IMPROVEMENT
1. SHEET G1.0; CODE INFORMATION (APPLICABLE CODES): IT IS NOTED THAT THE 2015 INTERNATIONAL CODES WERE USED FOR THIS PROJECT. AN APPEAL TO THE BUILDING OFFICIAL IS REQUIRED TO USE THE 2015 EDITIONS SINCE THE CITY OF TUCSON USES THE 2012 EDITIONS.
2. SHEET G1.0; CODE INFORMATION (MERCANTILE ALLOWABLE FLOOR AREAS): PER THE IBC TABLE 1004.1.2, MERCANTILE AREAS ON OTHER FLOOR IS LISTED AS 60 SF/PERSON AND 30 SF/PERSON AT BASEMENT AND GRADE FLOOR AREAS. THESE DO NOT AGREE WITH THE NUMBERS ON SHEET G1.0. PLEASE COORDINATE.
3. SHEET D1.0; DEMOLITION PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES ON THE PLAN.
4. SHEET D1.0; STOREFRONT DEMOLITION: IT IS NOT CLEAR ON THE ELEVATION WHAT IS BEING REMOVED. PLEASE CLARIFY AND REFERENCE SHEET A2.0.
5. SHEET D1.0; DEMOLITION PLAN: PLEASE INDICATE NORTH ARROW ON THE PLAN.
6. SHEET A1.0; CONSTRUCTION PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES AND DIMENSIONS ON THE PLAN.
7. SHEETS A1.0, A3.0, A5.0, AND A6.0; PLANS: PLEASE INDICATE NORTH ARROWS ON THE PLANS.
8. SHEET A1.0; CONSTRUCTION PLAN: THE PARTITION TYPE AT THE UPPER WALL (NEAR GRID 3) INDICATES AN A2 AND G WALL. SHOULD THIS ALSO INCLUDE AN A3 PARTITION TYPE? PLEASE VERIFY.
9. SHEET A1.0; CONSTRUCTION PLAN: THE PARTITION TYPE AT THE LOWER WALL INDICATES AN A2 WALL. SHOULD THIS ALSO INCLUDE AN A3 PARTITION TYPE? PLEASE VERIFY.
10. SHEET A1.0; CONSTRUCTION PLAN: PLEASE INDICATE THE EXTERIOR WALL TYPE ALONG GRID 4 OF THE TENANT SPACE.
11. SHEET A1.0 (CONSTRUCTION PLAN); SHEET A1.1 (PARTITION TYPE): THE PARTITION TYPE C (LOCATED AT THE FITTING ROOM AND VESTIBULE AREA) SHOULD INDICATE ON SHEET A1.1 THE METAL JOISTS, PLYWOOD, AND CEILING COMING INTO THE PARTITION AT A LOWER LEVEL (SIMILAR TO PARTITIONS D AND E). PLEASE VERIFY.
12. SHEET A1.0 (CONSTRUCTION PLAN); SHEET A1.1 (PARTITION TYPE): THE PARTITION TYPE C (LOCATED AT THE PASSAGE AREA) SHOULD INDICATE ON SHEET A1.1 THE METAL JOISTS, PLYWOOD, AND CEILING COMING INTO THE PARTITION AT A LOWER LEVEL (SIMILAR TO PARTITIONS D AND E). PLEASE VERIFY.
13. SHEET A1.0 (CONSTRUCTION PLAN); SHEET A1.1 (PARTITION TYPE): PARTITION TYPE A1 (ALONG GRID 1) IS TITLED AS A DEMISING PARTITION. THIS IS AN EXTERIOR WALL. PLEASE REVISE.
14. SHEET A1.1; SHEET S2.0: PLEASE ADD A NOTE ON SHEET A1.1 TO REFERENCE SHEET S2.0 FOR PARTITION DETAILS.
15. SHEET A1.2; PLAN 9: THIS PLAN SHOULD BE TITLED THE PASSAGE PLAN. PLEASE REVISE.
16. SHEET A1.3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE TOILET ROOM GENERAL NOTES.
17. SHEET A2.1; SECTION 1: A DETAIL AT THE TOP OF THIS SECTION IS NOT COMPLETE. PLEASE REVISE.
18. SHEET A3.0; FINISH PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES AND DIMENSIONS ON THE PLAN.
19. SHEET A5.0; FIXTURE PLAN: THIS SPACE REQUIRES TWO EXITS PER THE IBC TABLE 1015.1. SECTION 1014.2(4) EXCEPTION 2 ALLOWS EGRESS THROUGH MERCANTILE STORAGE ROOMS IF CRITERIA 2.1, 2.2, 2.3, AND 2.4 ARE MET. VERIFY THE NON-SALES AREA (STORAGE) MEETS THAT CRITERIA. IN ADDITION, IT APPEARS THE RECEIVING AREA COULD CREATE DEAD END EGRESS PATHS. PLEASE ADDRESS THIS ISSUE.
20. SHEET A5.0; FIXTURE PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES AND DIMENSIONS ON THE PLAN.
21. SHEET A6.0; REFLECTED CEILING PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES AND DIMENSIONS ON THE PLAN.
22. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/10/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE PROVIDE FULL COMPLIANCE WITH THE 2012 IECC FOR THE LIGHTING.