Permit Number: T17CM01024
Parcel: 11904600L

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM01024
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2017 ANDREW CONNOR ZONING REVIEW Approved
02/08/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
02/08/2017 MARTIN BROWN FIRE REVIEW Approved
02/10/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS.
#1.ASSIGN A SYMBOL OR ID EACH LUMINAIRE AND PROVIDE A COMPLETE LUMINAIRE SCHEDULE.
#2.REMOVE REFERENCES TO THE 2012 IRC. THIS BUILDING IS COMMERCIAL AND THE CODE FOR ELECTRICAL SHOULD BE 2011 NEC.
#3. PROVIDE COMPLIANCE WITH THE 2012 IECC FOR LIGHTING.
REF: 2012 IBC 107.2.1, 2011 NEC, 2012 IECC.
Dan.santacruz @tucsonaz.gov
02/10/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
02/10/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/10/2017 ROBERT SHERRY WATER REVIEW Completed
02/10/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/10/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/14/2017 ARUIZ1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/14/2017 ARUIZ1 OUT TO CUSTOMER Completed