Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM01024
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/08/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
02/08/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
02/08/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
02/10/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. #1.ASSIGN A SYMBOL OR ID EACH LUMINAIRE AND PROVIDE A COMPLETE LUMINAIRE SCHEDULE. #2.REMOVE REFERENCES TO THE 2012 IRC. THIS BUILDING IS COMMERCIAL AND THE CODE FOR ELECTRICAL SHOULD BE 2011 NEC. #3. PROVIDE COMPLIANCE WITH THE 2012 IECC FOR LIGHTING. REF: 2012 IBC 107.2.1, 2011 NEC, 2012 IECC. Dan.santacruz @tucsonaz.gov |
02/10/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
02/10/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/10/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
02/10/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
02/10/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/14/2017 | ARUIZ1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/14/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |