Permit Number: T17CM00997
Parcel: 132171260

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM00997
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2017 STEVE SHIELDS ZONING REVIEW Reqs Change P&DS TRANSMITTAL


FROM: Steve Shields,
Principle Planner

PROJECT:
T17CM00997
4233 S. Fremont Avenue
Covered parking structures for solar

TRANSMITTAL: February 16, 2017


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the I-1 zone (UDC 4.7.29). A warehouse is a permitted use in this zone (Table 4.8-5). See Use-Specific Standards 4.9.10.A and 4.9.13.Q.

The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall (UDC 6.4.5.C.1.a). Based on a height of 11'-6" the required front street perimeter yard is 20'-0", provided is 13'-3".
02/21/2017 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change Approval of the development package is required prior to approval of this plan.
02/27/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/09/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/16/2017 ARUIZ1 OUT TO CUSTOMER Completed