Permit Number: T17CM00976
Parcel: 13705494B

Review Status: Completed

Review Details: REVISION - - 8TH

Permit Number - T17CM00976
Review Name: REVISION - - 8TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved Please address the electrical review comment.
Per the revision letter submitted and dated April 25, 2022. Revision on plan sheet E2.3, states that a new meter pedestal 'MP5' is called out to be installed. Please indicate the located Pedestal with a cloud and Delta at its location on the electrical distribution plan or site plan.
Ref 2018 IBC 107.2.1, 2017 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/05/2022 VVERA1 OUT TO CUSTOMER Completed