Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 8TH
Permit Number - T17CM00976
Review Name: REVISION - - 8TH
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Please address the electrical review comment. Per the revision letter submitted and dated April 25, 2022. Revision on plan sheet E2.3, states that a new meter pedestal 'MP5' is called out to be installed. Please indicate the located Pedestal with a cloud and Delta at its location on the electrical distribution plan or site plan. Ref 2018 IBC 107.2.1, 2017 NEC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/05/2022 | VVERA1 | OUT TO CUSTOMER | Completed |