Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM00924
Parcel: 138244040

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM00924
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2017 ANDREW CONNOR ZONING REVIEW Approved
02/03/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Verify that the "integral factory return air smoke detector" for HP-1 will be located upstream of any outside air connections. Reference: Section 606.2.1, IMC 2012.
02/03/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENT.
REF: PLAN SHEET E2.0. THE TWO NOTES #19 AND #20 FOR THE POWER PLAN ( EQUIPMENT #20 ) ARE NOT FOUND ON THE PLAN.
02/03/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
02/03/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that hot water is being supplied to the lavatory. Reference: Section 607.1, IPC 2012.
2. Verify that the Rheem concentric vent kit is compatible with the Rennai instantaneous water heater. Reference: Section 303.2, IPC 2012.
3. Coordinate details 1/P2.0 and 3/A3.0.
02/03/2017 ROBERT SHERRY WATER REVIEW Completed
02/06/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET TS1; PROJECT CODE REVIEW: SPACE 4 IS INDICATED AS A 'B' USE. THIS IS A CARRYOUT ONLY, THEREFORE THE USE WOULD FALL UNDER RETAIL (M) OR FACTORY (F1). PLEASE REVISE.
2. SHEET K1.0; HOOD SUPPORT DETAIL: PLEASE REMOVE THIS DETAIL FROM THIS SHEET.
3. SHEET A1.0; FLOOR PLAN: IS THE RESTROOM ACCESSIBLE FROM THE BACK DOOR? A SIGN SHOULD BE INSTALLED TO INDICATE THE ACCESSIBLE RESTROOM ROUTE (CAN NOT GO THROUGH THE KITCHEN/JANITOR AREAS.
4. SHEET A2.0; TOILET ELEVATIONS A AND B: PLEASE ADD DIMENSIONS ON THE ELEVATIONS TO LOCATE ALL GRAB BARS AND TO INDICATE GRAB BAR LENGTHS PER THE ICC/ANSI A117.1 FIGURES 604.5.1 AND 604.5.2.
5. SHEET A3.0; DETAIL 3: A NOTE AT THE BOTTOM OF THE DETAIL INDICATES 'HORIZONTAL ANGLES TOP AND BOTTOM'. THE NEXT NOTE UP INDICATES 'ANCHOR TO WALL IN APPROVED MANNER'. PLEASE INDICATE THE ANGLE SIZES AND THE SIZE AND NUMBER OF CONNECTORS TO THE WALL.
6. SHEET A3.0; SECTION 4: AT THE UPPER PART OF THIS SECTION, PLEASE INDICATE THE SIZE AND NUMBER OF CONNECTORS FOR THE VERTICAL STUDS AND LATERAL BRACE STUDS.
7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/06/2017 MARTIN BROWN FIRE REVIEW Approved
02/06/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved